A gas detector that has not been tested is only an assumption. Sensors age, get poisoned by silicones or high concentrations, and drift with temperature and humidity. Bump testing and calibration are how you prove the detector will alarm when it matters.
Bump test vs calibration
- Bump test: a short exposure to a known gas to check that the sensors respond and the alarms (audible, visual, vibration) work. It does not adjust the readings.
- Calibration: exposing the detector to certified gas of known concentration and adjusting the reading so it matches. It corrects drift and restores accuracy.
How often?
- Portable detectors: most manufacturers recommend a bump test before each day's use and a full calibration at regular intervals, typically every 6 months or as the manufacturer specifies, and after any failed bump test.
- Fixed detectors: functional test and calibration at least every 6 to 12 months depending on the sensor, the gas and the site risk, plus a check of the control panel, relays, sounders, beacons and shut-off valves.
What a professional service includes
- Inspection, cleaning and filter replacement.
- Calibration with traceable, certified gas cylinders.
- Alarm set-point and output checks (4-20 mA, relays, Modbus).
- Sensor replacement when the sensor reaches end of life.
- A calibration certificate for each instrument, ready for audits.