Refrigerant Gas Detection in Machinery Rooms: What EN 378 Requires

21.11.26 10:54 PM By Mohamed Eltelbany

Chillers, cold stores, supermarkets and HVAC plant rooms hold large charges of refrigerant. A leak can displace oxygen, create a toxic or flammable atmosphere (ammonia, A2L and A3 refrigerants) and cost money in lost refrigerant and downtime. Refrigerant gas detection is therefore both a safety and an environmental requirement.

What the standard says

EN 378-3 states that at least one detector shall be installed in each machinery room, or in the occupied space being considered, where the refrigerant concentration could exceed the practical limit. The detector must trigger an alarm and start the emergency ventilation. Other standards that apply include EN 14624, ISO 5149-3 and the EU F-Gas Regulation.

Match the detector to the refrigerant

  • HFC and HFO refrigerants (R32, R134a, R404A, R410A, R1234yf, R1234ze, R454B and others): infrared or semiconductor sensors.
  • Ammonia (R717): electrochemical sensors for toxic levels, catalytic for high concentrations in plant rooms.
  • CO2 (R744): infrared sensors.
  • Hydrocarbons (R290 propane): flammable gas detectors in %LEL.

Where to install

Most refrigerants are heavier than air, so detectors usually go low, about 20 cm above the floor, close to compressors, valves and joints where leaks start. Ammonia is lighter than air, so its detectors go high. In cold rooms, install the detector in the return air flow.

Detectors we supply

  • Sensitron SMART 3-R: designed for machinery rooms, laboratories and safe areas, with visual and audible alarms, 4-20 mA, RS485 and relay outputs, and compliance with EN 378-3, EN 14624 and ISO 5149-3.
  • Sensitron SMART 3 Blizzard: infrared refrigerant detector for HVAC-R systems and machinery rooms, SIL 2 certified, for gases such as R32, R454B and R410A.
  • Sensitron SMART 3G: ATEX versions for refrigerants in classified areas, including ammonia plant rooms.
  • Tecnocontrol TS281 / TS282: industrial refrigerant and ammonia detectors with 4-20 mA output.

Tetratech supplies, installs and calibrates refrigerant detection systems across Egypt. Browse refrigerant detectors or ask our engineers.

Sources: Sensitron SMART 3-R and SMART 3 Blizzard documentation; EN 378-3:2016 section 9.