Sensitron Smart 3G-D2 Pentane Gas Detector, 0-100% LEL, Catalytic Sensor, ATEX Zone 1 – S2157PE. Applications: Oil & gas facilities and refineries, Petrochemical & chemical plants. Supplied, installed and calibrated in Egypt by Tetratech, authorized Sensitron distributor.
Tags:
Product Details
Product Details
Product Details
The Sensitron SMART 3G-D2 is an explosion-proof fixed gas detector with a 4-digit display showing gas concentration in real time. It is certified for ATEX Zone 1 and detects flammable, toxic, refrigerant gases and oxygen.
Key features
- Non-intrusive one man calibration via Hall effect switches
- 4-digit display and 5 mode status LEDs
- Multi-color LED light ring
- Standard 4-20 mA 3 wire output
- Standard 3 relay output
- Optional RS485 interface for Modbus communication
- Zero tracking to maintain the zero point steady from possible drifts
- Ongoing system self diagnosis ATEX II 2G Ex db IIC T5 Gb (standard marking)
- ATEX II 2GD Ex db IIC T5 Gb (II2 GD with optional adapter to be specified at the order)
- ATEX II 2G Ex db [ib] ib IIC T6 Gb for detectors with intrinsically safe protection
Technical specifications
| Brand | Sensitron |
|---|---|
| Manufacturer | Sensitron SRL |
| Model / series | Smart 3G-D2 |
| Part number (SKU) | S2157PE |
| Product type | Fixed Gas Detector |
| Target gas | Pentane |
| Measuring range | 0-100% LEL |
| Sensor technology | Catalytic |
| Certification / protection | ATEX Zone 1 |
| Power supply | 12-24 Vdc |
| Max. power | 5.4 W |
| Outputs | 4-20 mA (3-wire); 3 relays (1 A @ 24 Vdc); optional RS485 Modbus |
| Sensor | Catalytic (pellistor) |
| Response time | T90 < 60 s |
| Expected sensor life | 4-5 years |
| Operating temperature | -40 to +60 °C |
| Operating humidity | 20-90% RH @ 40 °C |
| Enclosure | Aluminium pressure die-cast, epoxy painted, explosion-proof (Ex d); stainless steel sensor head |
| Dimensions | 145 x 187 x 108 mm |
| Weight | 1900 g |
| Cable entries | 2 x 3/4" NPT |
| IP rating | IP65 |
| ATEX marking | II 2G Ex db IIC T5 Gb (II 2GD Ex db IIC T5 Gb / Ex tb IIIC T100°C Db with optional dust adapter) |
| IECEx marking | Ex db IIC T5 Gb |
| Hazardous area | Zone 1 and Zone 2 (gas); Zone 21/22 with dust adapter |
| SIL | SIL2 hardware / SIL3 software (SIL3 hardware in redundant configuration) |
| Display | 7-segment gas display, 5 status LEDs, 4 smart LEDs |
Applications
- Oil & gas facilities and refineries
- Petrochemical & chemical plants
Supplied, installed and calibrated in Egypt by Tetratech, authorized Sensitron distributor. Request a quote for pricing, availability and technical support.